Service:Liquids, powder and bulk materials compatible with wetted materials.Wetted Materials:316 SS and polyvinylidene fluoride (PVDF).Temperature Limits:Ambient: -40 to 185°F (-40 to 85°C), -4 to 185°F (-20 to 85°C) with under 24 VAC/DC power supply;
Process: -40 to 250°F (-40 to 121°C).Pressure Limit:365 psi (25 bar).Enclosure Rating:Weatherproof, NEMA 4X.Switch Type:DPDT (two form C).Electrical Rating:8 A @ 120/240 VAC res., 30 VDC. 1/2 hp @ 120 VAC and 1/4 hp @ 240 VAC ind.Power Requirements:12 to 240 VAC/DC.Power Consumption:2.8 Watts max.Electric Connections:1/2″ NPT conduit opening, screw termination and removable terminal block.Process Connection:See Catalog Page.Mounting Orientation:Vertical or horizontal.Set Point Adjustment:Trips when product touches probe. Cut or extend probe to length of desired trip point. Can be cut as short a 1″ and can be extended by welding on to probe. (Minimum length will be effected by material being sensed.)Response Time:0.2 s.Time Delay:Adjustable, 0 to 60 s.Spark/Static Protection:10 MEG Ohm dissipation resistance with spark gap. Surge current to 100A max.Sensitivity:8 selectable settings, 1, 2, 4, 6, 8, 10, 14, 20 pF (at 30 pF nominal free capacitance).Agency Approvals:CE, cULus.